Cooling Water Circulator (Externally Closed Circulation, Air Cooling) (CFA302)

Precision external closed cooling water circulator with the temp. control accuracy±0.1°C.

Features of Cooling Water Circulator (Externally Closed Circulation, Air Cooling) (CFA302)

Category:

Description

Features

Provide high-precision circulation water with the temp. range -10°C+80°C (CFA611/CFW611) and temp. control accuracy±0.1°C.

Features

Powerful cooling capacity.

Features

Continuous monitoring for water level, abnormal refrigerator pressure, refrigerator operation, circulation pump operation, etc..

Features

Configurated with auto stop, auto start operations, temp. output terminal, deviation correction, external communication (RS485), etc..

Safety Features

Overcurrent ELB, self-diagnosis, key lock, refrigerator overload protector, refrigerator delay timer of protection, refrigerator pressure detection, float switch preventing pump idling, bypass for protecting circulating pump, auto overheat protection, overheat protector, etc..

Model CFA302
Method External closed circulation
Operating temperature range -10 to +60°C
Temperature control accuracy ±0.1°C JTM K05 (at 20°C)
Temperature setting, display Digital setting and display
Temperature indicating unit 0.1°C
Cooling capacity Approx. 370W (318Kcal/h), at fluid temp.10°C
Operating environmental temp. range 5 to 35°C
Temperature control PID control
Temperature sensor Temp. controller: Pt thermal resistance, overheat protection: K thermocouple
Refrigerator, refrigerant Air cooling 300W, R404A
Circulating pump Magnetic drive pump 45W
Unit circulation ability (50/60Hz) Max. flow, Pump capacity 8.9 / 10.3L/min (15 / 17L/min)
Unit circulation ability (50/60Hz) Max. lift, Pump capacity 6.6 / 9.0m (8.0 / 11.0m)
Heater Stainless steel heater 850W
Cooling coil Nickel-clad copper
External circulation nozzle Rc3/8 (CFA301 standard configuration pagoda connector)
Safety device Overcurrent ELB, Self-diagnosis, Refrigerator overload protector, Refrigerator delay timer of protection, Refrigerator pressure detection, Float switch preventing pump idling,
Safety device Bypass for protecting circulating pump, Auto overheat protection, Overheat protector, etc..
Other functions Drain valve, Condenser filter screen, Deviation correction, External communication (RS485), Refrigerator pressure indicator, Key lock, Temp. output terminal
Accessories Drain pipe, Overflow pipe
External dimensions(W×D×H mm) 380×565×725mm
Remarks(dimensions) Bath capacity 13L, W245×D315×H180mm
Power Source AC115V/AC220V
Single-phase with step down transformer
Weight 60kg